An overcurrent is caused by a short-circuit, ground-fault, or an overload.
A short-circuit may be hundreds or even thousands of times above the normal operating current. This type of fault may be an arcing fault between ungrounded conductors or between an ungrounded conductor and a grounded (usually, a neutral) conductor, a line-to-line arcing fault may produce a current of 74% of a 3-phase bolted fault. A line-to-neutral arcing fault will be somewhat less.
A line-to-line bolted fault, the equivalent, of the conductors bolted together, may be up to 100% of the available short-circuit current.
A line-to-neutral bolted fault may be in excess of 100% of the 3-phase bolted fault at the source, but considerably less downstream.
A ground-fault, that is, the equivalent of a connection between an ungrounded conductor and the equipment grounding system, will produce a current that may be 38% or higher of the 3-phase bolted fault current. These types of faults are typically arcing faults which normally are intermittent in nature. That is, they strike and restrike over time and may produce a short-circuit fault due to insulation damage.
Once again, a line-to-equipment ground fault near the source may produce a fault current of over 100% of the 3-phase bolted fault, but considerably less downstream.
An overload typically ranges from one to six times the normal current, and are normally caused by motor starting currents or transformer magnetizing currents. These conditions are of such short duration that the circuit components are not damaged.
This book has a detailed analysis of these types of faults, along with explanations and examples of the various types of overcurrent protective devices to assure proper protection.
This volume has extensive information on the application of overcurrent protection for conductors and equipment. The reader will be able to calculate fault currents as well as establishing the short-circuit withstand rating of conductor insulation and to determine the appropriate type of overcurrent devices based on circuit conditions.
In addition, determining ground-fault currents for the purpose of selecting the proper size of equipment grounding conductors to establish an effective ground-fault current path is discussed in detail.
Readership - Anyone involved with the design of overcurrent protection for electrical distribution systems from the system source to the electrical utilization equipment. The emphasis is placed on the design of the overcurrent protection for specific installations to assure proper protection for the circuit components regardless of the type of fault encountered.
저자소개
Gregory P. Bierals, President, Electrical Design Institute, LLC-has presented seminars worldwide on various topics including the National Electrical Code, Grounding Electrical Distribution Systems, Designing Overcurrent Protection, Electrical Equipment Maintenance, and Designing Electrical Systems for Hazardous (Classified) Locations. He has maintained an extensive client list during the past 45 years, and he has earned the reputation of being an extraordinary lecturer as a result of his organization of materials and knowledge of this subject.
교환/반품 안내
반품/교환 방법 | 마이페이지 > 고객센터 1:1문의 작성 또는 고객센터 (02-322-2426) |
---|---|
반품/교환가능 기간 | 변심반품의 경우 수령 후 7일 이내, 상품의 결함 및 계약내용과 다를 경우 문제점 발견 후 30일 이내 파본 등 상품결함 시 '문제점 발견 후 30일(단, 수령일로 부터 3개월)' 이내 |
반품/교환비용 | 변심 혹은 구매착오로 인한 취소/반품은 판매가의 20% 취소수수료 고객 부담 * 취소수수료 : 수입제반비용(국내 까지의 운송비, 관세사비, 보세창고료, 내륙 운송비, 통관비 등)과 재고리스크(미판매 리스크, 환차손)에 따른 비용 등 단, 아래의 주문/취소 조건인 경우, 취소 수수료 면제 오늘 00시~06시 주문시 오늘 06시 이전 취소 오늘 06시 이후 주문 후 다음 날 06시 이전 취소 |
반품/교환 불가 사유 | 1) 소비자의 책임 있는 사유로 상품 등이 손실 또는 훼손된 경우 (단지 확인을 위한 포장 훼손은 제외) 2) 소비자의 요청에 따라 개별적으로 주문 제작되는 상품의 경우 3) 시간의 경과에 의해 재판매가 곤란한 정도로 가치가 현저히 감소한 경우 4) 전자상거래 등에서의 소비자보호에 관한 법률이 정하는 소비자 청약철회 제한 내용에 해당되는 경우 |
상품 품절 | 공급사(출판사) 재고 사정에 의해 품절/지연될 수 있으며, 품절 시 관련 사항에 대해서는 이메일과 문자로 안내드리겠습니다. |
소비자 피해보상 환불 지연에 따른 배상 | 1) 상품의 불량에 의한 교환, A/S, 환불, 품질보증 및 피해보상 등에 관한 사항은 소비자분쟁 해결 기준에 준하여 처리됨 2) 대금 환불 및 환불지연에 따른 배상금 지급 조건, 절차 등은 전자상거래 등에서의 소비자 보호에 관한 법률에 따라 처리함 |
장바구니로 이동하시겠습니까?
긴급배송
일반배송